Application: | High-voltage, Low-voltage, High-temperature |
---|---|
Material: | Glass |
Structure: | AC Standard Glass Insulator |
Still deciding? Get samples of US$ 0/Piece
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Type | Diameter (mm) | Structural Height (mm) | Creepage Distance (mm) |
Coupling Size (mm) | Specified Mechanical Load(kN) | Dry Power Frequency Withstand Voltage 1 minute (kV) | Wet Power Frequeney Withstand Voltagesingle unhit /shorlt 'string with 5 PCS (kV) |
Dry Lightning Impullse Withstand Voltagesingle unit /short string with SPCS (kV) | Min power Frenquency Puncture Voltage (kV) | Net Weight Per Unit(kg) |
U70B/146 | 255 | 146 | 320 | 16 | 70 | 70 | 40/180 | 100/420 | 130 | 3.6 |
U100B/146 | 255 | 146 | 320 | 16 | 100 | 70 | 40/180 | 100/420 | 130 | 3.6 |
U120B/146 | 255 | 146 | 320 | 16 | 120 | 70 | 40/180 | 100/420 | 130 | 3.6 |
U160B/155 | 280 | 155 | 400 | 20 | 160 | 75 | 45/200 | 110/500 | 130 | 6.5 |
U210B/170 | 280 | 170 | 400 | 20 | 210 | 75 | 45/200 | 110/500 | 130 | 7.0 |
U240B/170 | 280 | 170 | 400 | 24 | 240 | 75 | 45/200 | 110/500 | 130 | 7.2 |
U300B/195 | 320 | 195 | 485 | 24 | 300 | 85 | 50/200 | 130/500 | 130 | 9.7 |
U300B2/195 | 330 | 195 | 550 | 24 | 300 | 90 | 55/200 | 140/550 | 130 | 10.8 |
U420B/205 | 360 | 205 | 550 | 28 | 420 | 90 | 55/200 | 140/550 | 130 | 13.0 |
U550B/240 | 360 | 240 | 635 | 32 | 550 | 95 | 55/200 | 150/650 | 130 | 17.5 |
U760B/280 | 400 | 280 | 710 | 36 | 760 | 100 | 60/260 | 150/720 | 130 | 26.3 |
U840B/300 | 400 | 300 | 710 | 40 | 840 | 100 | 60/260 | 150/720 | 130 | 27 |
Order Information: 1. Voltage grade; 2. Specified mechanical load; 3. Creepage distance; 4.Power frequency withstand voltage; 5. Lightning Impulse Withstand Voltage; 6. Insulation distance; 7. Coupling type; Ps. Different end fittings could be supplied as customer requirements |